When It Comes to Pressure & Temperature Switches, Understand the Difference Between Switch Normal and Process Normal

Diagram of pressure switch
Diagram of pressure
switch. Note the SPDT
electrical switch on top.
  (Courtesy of United
Electric Controls
)
The normal status of a switch can be a confusing aspect of understanding the function of connected electrical and logic components in a process control application. The misunderstanding stems from the ambiguity of the word normal. Typically, electrical switch contacts are classified as being normally-open or normally-closed, referring to the open or closed status of the contacts under normal conditions. The key in understanding the normal state of a switch contact requires one to dissociate from their thinking, the concept or definition of normal used in everyday conversation. Where, among friends in casual conversation, the word normal tends to refer to what is expected, the normal status of the switch is, explicitly, its contacts electrical status when no stimulus is applied, that is, when the switch is at rest. An applied example of this definition is a momentary-contact pushbutton switch is not being pressed, because, when the pushbutton is not being pressed, the switch is experiencing no physical stimulation. Electrical schematic drawings always represent switches in their normal status. When an electrical switch on a lamp is in its normally-open state, the switch is open while receiving no physical stimulation.

Temperature switch (UEC)
Temperature switch (courtesy of
United Electric Controls)
The concept of normal is somewhat more complex when applied to pressure and temperature switches. Pressure and temperature switches are actuated, not by electrical signal or human contact, but by process related stimuli, i.e. temperature, flow, pressure, or level. A flow switch is actuated by a defined amount of flow through a pipe.  Lets say a flow switch is engineered to trigger an alarm when the flow rate inside a pipe is below a certain level. Even if the contacts of the flow switch are designated as being in their normally-closed status, the switch will be open when enough fluid is flowing through the pipe. The normal switch status (closed) indicates an abnormal process flow rate condition, because the switch is only going to be in its normal electrical status when the flow is low. Considering this inverse nature (normal switch status indicating abnormal process status), switch contacts are conventionally represented in accordance with the switch operation and not the process operation. The manufacturers of the pressure and temperature switches cannot predict the normal status of particular processes in which their switches will be used. By utilizing the conventional switch terminology, there is a common status designation for the normal status of the switch. The designation is applicable and readable regardless of the process conditions of the specific industry using the switch. This convention provides for universal comprehension of control system electrical schematics and other symbolic representations of control system operation.
Pressure switch
Pressure switch (courtesy of
United Electric Controls)

In making the connection between the normal state of switch contacts and the normal state of a process, one should relate the switch state to the process condition which would serve as the stimulus to change the switch state. For a limit switch, which responds to physical contact by an object, normal means the target is not contacting the switch. For a proximity switch, normal means the target is far away. A normal pressure switch condition occurs when the pressure is low, or may even indicate a vacuum. Level switches are normal when the level is empty. Normal for a temperature switch means the temperature is low. Flow switches are normal when there is a low flow rate, or the fluid is stopped. Both an understanding of normal as defined by the manufacturer of the switch and normal in terms of industry specific processes is necessary to correctly interpret the status of an operation. Once the concept of normal used in everyday conversation is uncoupled from your process control thinking, things fall into place easily.

Industrial Control Valve Actuator Operating Principles

Control valve actuators control fluid in a pipe by varying the orifice size through which the fluid flows. Control valves contain two major components, the valve body and the valve actuator. The valve body provides the fluid connections and immovable restrictor comprised a valve stem and plug that is in contact with the fluid that varies the flow.

The valve actuator is the component that physically moves the restrictor to vary the fluid flow. Three actuator types are used in control valves and they include spring and diaphragm, solenoid, and motor. As the name suggests the spring in diaphragm actuator uses a spring and a diaphragm to move the valve stem and plug.

A 15 PSI pneumatic signal enters the housing at the top of the actuator. As pressure is exerted on the diaphragm a downward force is applied against the spring which moves the restrictor. The diaphragm moves until it creates an equal but opposing force against the spring at which time the motion stops as the plug meets the valve seat. With no air pressure the restrictor is pushed upward by the spring to act as a normally open control valve. To vary the position of the restrictor and flow through the valve, a current to pressure transducer can be used to provide a three to 15 PSI signal to the diaphragm.  At 3 PSI the valve is maintained open, and 15 PSI the valve is maintained closed. Pressures between the three to 15 PSI range proportionally change the flow of the valve. For example a pressure of 9 PSI applied to the diaphragm moves the spring and valve stem to 50 percent operating range.

For on /off control of the valve, a solenoid is used to actuate the valve to a fully closed or fully open position. Applying current to the coil generates a magnetic field that moves the plunger downward against the return spring. With zero current applied to the coil the spring pulls the plunger upwards to the fully open position for a normally open state control valve.

Another method for variable valve positioning uses a motor and is referred to as proportional control mode. Using a gear motor attached to the valve stem a servo amplifier provides a DC control signal that moves the valve to the desired position. Feedback is achieved with the wiper arm attached to the valve stem that sends a signal back to the servo amplifier where the position is monitored the servo amplifier drives the motor until the control signal is equal to the feedback signal.

Watch the video below for an illustrated explanation. For more information on control valves, contact Ives Equipment at 877-768-1600 or visit http://www.ivesequipment.com.

SITRANS FC430 Coriolis Flowmeter Wins Control Engineering’s 2017 Engineers’ Choice Award

SITRANS FC430 Coriolis flow meter
SITRANS FC430 Coriolis Flow Meter
The Siemens SITRANS FC430 Coriolis flow meter, with National Type Evaluation Program custody transfer approval, for volume and mass liquid flow,  is a Control Engineering 2017 Engineers’ Choice Awards Winner.

The Siemens SITRANS FC Coriolis flow sensor delivers mass flow, volume flow, density, fraction and temperature measurement of both liquids and gases with exceptionally high accuracy and low pressure drop.

Siemens Coriolis flow meters are user-friendly to set up and use day-to-day. The meters stand up to the most demanding process industry conditions and continue to operate in the noisiest of environments – from hazardous chemicals to fiscal metering, custody transfer to compressed natural gas fuel dispensing. Its compact design makes installation easy even in the tightest spaces.

For more information on Siemens products, visit Ives Equipment here or call (877) 768-1600.

An Extremely Thin, Multipoint, Temperature Measuring System

SITRANS TO500
Example of use (click for larger view)
Do you want to install a very large number of measuring points in the smallest possible space with a low thermal mass?

Recognizing temperature profiles and detailed understanding of the process are great challenges to plant operators. A fiber-optic based multipoint measuring system by SIEMENS enables you to determine a large number of temperature measuring points along a single sensor fiber and read out a temperature profile in a matter of seconds.

For example, you can quickly and precisely identify points overheating to help avoid or counteract potential damage to your product and/or equipment. Measured values are transmitted through an extremely thin sensor measuring lance. The diameter of the sensor measuring lance is independent of the number of measuring points. The response times of the sensors are also reduced because of the low thermal mass of the fiber optic.

Operation:

A continuously tunable laser generates light in the transmitter with a wavelength between 1500 and 1600 nm, which is output to the sensor measuring lances. The transmitter evaluates the reflected light component. Fiber Bragg Gratings (FBG) are inscribed at defined points on the sensor measuring lances, that reflect a defined wavelength. The wavelength reflected by the grating changes as a function of temperature and so indicates the temperature at the relevant measuring point. A gas cell with a fixed absorption line serves as a reference in the device, against which the determined wavelength is continuously calibrated.
SITRANS TO500
Design of fiber measuring sensor (click for larger view)


SITRANS TO500
In use measuring catalytic conversion
of gases in tube and tube-bundle reactors.
Typical applications:
  • Tube and tube-bundle reactors
  • Capillary and microreactors
  • Distillation
  • Rectifications
For more information in the SITRANS TO500 visit Ives Equipment or call (877) 768-1600.

Industrial, Fixed Point Gas Detection and Monitoring

Gas detection
Toxic / Flammable
Gas Detection
(courtesy of Sensidyne)
In industry, the assessment and control of risk factors is a crucial element of process control. Commanding risk allows not only for peace of mind regarding environments involving hazardous materials, but also ensures - and prioritizes - the safety of those who work with said materials. Fixed point gas monitoring tracks and repeatedly evaluates the levels of potentially toxic or flammable gases in an industrial environment, typically using electrochemical, infrared, or catalytic bead sensors. A central monitoring station allows for an entire facility to operate under consistent watch, as the array of gas monitors throughout a facility form a system. Typical environments which utilize fixed point gas monitoring include CNG filling stations, fleet maintenance buildings, wastewater lift stations and treatment plants, pipelines, and refineries, among others.

Due to the variation in facilities and associated industrial purposes, the applicability and customization of fixed point monitors must be adaptable. The gases typically monitored by fixed point systems are industrial staples. Natural gas (methane) and hydrogen are inherently dangerous to work with due to both their combustible nature and flammability. Carbon monoxide, hydrogen sulfide, and chlorine are especially dangerous to those who work in and around facilities where they are used or produced, while otherwise harmless gases such as nitrogen can cause oxygen displacement leading to asphyxiation. Around-the-clock is the only way to monitor and mitigate the potential impact of such volatile substances; thanks to automation, the ability to be constantly vigilant of threats related to gases is possible.
Gas detection
Hazardous Gas Sensor
(courtesy of Sensidyne)

Sensing and evaluating these types of gases is a complex process, yet one which also showcases the powers of the associated technology. International certification standards like ATEX (derived from a French regulation acronym) and SIL (the safety integrity level) allow designers of gas detectors to match their products with the necessary parameters to ensure safe working environments. For example, one manufacturer's electrochemical gas sensor operates based on a principle involving two electrodes; the first electrode senses the toxic gas, and then the second electrode receives protons generated by the sensing electrode through an ion conductor. Output current which flows to an external circuit is proportional to the concentration of gas, therefore the current generated is measurable as an indicator of gas levels. Despite the fact that these sensors are primarily used in industry, there is also the potential for domestic applicability, automotive process control, and air quality control, among other uses. The different technological and practical applications of fixed point gas monitors allow for industry professionals to safely and capably navigate working environmental hazards for personnel and process protection.

For more information on industrial gas detection and monitoring, visit Ives Equipment at http://www.ivesequipment.com or call (877) 768-1600.

Valve Actuators: An Overview

Rack & Pinion Actuated Valve
Rack & Pinion Actuated Valve
(courtesy of Flowserve Worcester)
Valves are essential to industries which constitute the backbone of the modern world. The prevalence of valves in engineering, mechanics, and science demands that each individual valve performs to a certain standard. Just as the valve itself is a key component of a larger system, the valve actuator is as important to the valve as the valve is to the industry in which it functions. Actuators are powered mechanisms that position valves between open and closed states; the actuators are controllable either by manual control or as part of an automated control loop, where the actuator responds to a remote control signal. Depending on the valve and actuator combination, valves of different types can be closed, fully open, or somewhere in-between. Current actuation technology allows for remote indication of valve position, as well as other diagnostic and operational information. Regardless of its source of power, be it electric, hydraulic, pneumatic, or another, all actuators produce either linear or rotary motion under the command of a control source.
Electric Valve Actuator
Electric Valve Actuator
(courtesy of Flowserve Worcester)

Thanks to actuators, multiple valves can be controlled in a process system in a coordinated fashion; imagine if, in a large industrial environment, engineers had to physically adjust every valve via a hand wheel or lever! While that manual arrangement may create jobs, it is, unfortunately, completely impractical from a logistical and economic perspective. Actuators enable automation to be applied to valve operation.

Pneumatic actuators utilize air pressure as the motive force which changes the position of a valve. Pressurized-liquid reliant devices are known as hydraulic actuators. Electric actuators, either motor driven or solenoid operated, rely on electric power to drive the valve trim into position. With controllers constantly monitoring a process, evaluating inputs, changes in valve position can be remotely controlled to provide the needed response to maintain the desired process condition.

Manual valve
Manual  cryogenic ball valve
(courtesy of Flowserve Worcester)
Manual operation and regulation of valves is becoming less prevalent as automation continues to gain
traction throughout every industry. Valve actuators serve as the interface between the control intelligence and the physical movement of the valve. The timeliness and automation advantages of the valve actuators also serve as an immense help in risk mitigation, where, as long as the system is functioning correctly, critical calamities in either environmental conditions or to a facility can be pre-empted and quickly prevented. Generally speaking, manual actuators rely on hand operation of levers, gears, or wheels, but valves which are frequently changed (or which exist in remote areas) benefit from an automatic actuator with an external power source for a myriad of practical reasons, most pressingly being located in an area mostly impractical for manual operation or complicated by hazardous conditions.

Thanks to their versatility and stratified uses, actuators serve as industrial keystones to, arguably, one of the most important control elements of industries around the world. Just as industries are the backbones of societies, valves are key building blocks to industrial processes, with actuators as an invaluable device ensuring both safe and precise operation.

Contact Ives Equipment with any valve automation requirement you may have.

Basics of Variable Area Flowmeters (Rotameters)

variable area flowmeter
Rotameter
(variable area flowmeter
courtesy of SIEMENS)
Rotameters (variable area flowmeters) can be used to measure many different types of liquids and gases passing through closed piping. The robust design means that it can also be used in harsh conditions. The various types of flange connections, linings and float materials satisfy the requirements of the pharmaceutical and chemical industries.

Flow measurement is performed according to the float principle. The flowing medium lifts the conical float in the measuring ring. This increases the ring gap until an equilibrium is established between the buoyant force of the medium and the weight of the float. The height of the float is directly proportional to the flow rate. The movement of the float is transmitted from one magnet to another magnet in the display unit outside of the measuring tube.

The devices are particularly suitable for measuring:
  • Water
  • Liquids
  • Anti-corrosives and lubricants
  • Solvents
  • Saturated and superheated steam • Food and beverages
  • Industrial gases
The video below provides and excellent understanding of how rotameters operate.